Draka LMCJ05004 Lifeline, 4/5C, MC LSZH, Two-Hour Fire Resistive Cables

SKU DLMCJ05004
How will you purchase this wire?
0.000000 0.000000
truck FREE SHIPPING ON ORDERS OVER $1000
MIN: 1 FT. | MAX: 10000 FT. 1 10000 tooltip To order multiple lengths, simply enter the desired footage into the quantity fields. Each length will be delivered on its own spool.

Please Select Color(s)

Multiple colors can be selected

....
Quantity

Select your preferred quantity for each color below. Add additional colors and lengths as needed.

Draka LMCJ05004 Lifeline, 4/5C, MC LSZH, Two-Hour Fire Resistive Cables

Color Length (ft.) Price
N/A

Length (ft.)

add Add a length
Grouped product items
Color Length (ft.)
N/A Length 500 ft.
truck FREE SHIPPING ON ORDERS OVER $1000
Product Details

Learn everything you want to know about this product to make an informed purchase

Specifications
  • # of Conductors

    5 Conductors

Data provided on this page is subject to change based on different manufacturers variances.
See Less
More information

Draka LMCJ05004 Lifeline, 4/5C, MC LSZH, Two-Hour Fire Resistive Cables

General Description

Lifeline MC LSZH fire resistive cables were designed to meet and have successfully passed the two-hour fire rating certification test per UL 2196, Standard for Tests for Fire Resistive Cables. Lifeline MC LSZH Cables are economical options for several life safety fire resistive applications in roadway and tunnel  environments with a LSZH jacket to protect against corro- sion. Fire resistive cables are required per NFPA 70, Articles 517, 695, 700, 708, 728 and 760 as well as NFPA 72 and NFPA 101.

Applications
- Emergency Feeder Cables
- Ventilating Fans
- Exit Lighting
- Emergency lighting and ventilation for roadway and transit tunnels



Specs and Ratings:
Listed to UL 1569, Metal Clad Cables, as the following type:
- Type MC 600 Volt, Rated 90°C
- For Wet Locations
- For Cable Tray Use IEEE 1202/ FT4 Rated, ST1 Limited Smoke
- Sunlight Resistance
- Direct Burial
- Classified to UL 2196, Standard for Tests for Fire Resistive Cables, for two-hours installations
- Electrical Circuit Integrity System (FHIT) No. 50 of the UL Fire Resistance Directory
- NFPA 70, NFPA 101, NFPA 130, NFPA 502 compliant
- Corrugated Copper Armor meets Equipment Grounding Conductor requirements of NEC Table 250.122



Conductor Size: 4 AWG
Conductors: 5
Conductor Material: Bare Stranded Copper
Insulation Material: Ceramifiable Silicone Zero Halogen (LSZH)
Outside Diameter: 1.70 Inches
Ampacity 75°C: 85
Ampacity 90°C: 95
Jacket Material: Thermoplastic Flame Resistant LSZH Jacket
Inner Binder Jacket: Ceramifiable Silicone Zero Halogen (LSZH)
Armor: Continuously Welded and Corrugated Copper
Net Weight: 1.20 lbs per ft

Spec Sheet

Belden 9841 Spec SheetView Spec Sheet for Complete Details

 

See Less