Draka LMC032/0 Lifeline, 2/0-3C, MC, Two-Hour Fire Rated Cables

Min: 1 ft., Max: 10000 ft. To order multiple lengths, simply enter the desired footage into the quantity fields. Each length will be delivered on its own spool.
Qty:
Qty:
Qty:
Qty:
Qty:
Qty:
Qty:
Qty:
Qty:
Qty:
Add a length

 Free Shipping on all orders over $1000

Draka LMC032/0 Lifeline, 2/0-3C, MC, Two-Hour Fire Rated Cables

SKU
DLMC032/0-FT

Product Details

Learn everything you want to know about this product to make an informed purchase

Draka LMC032/0 Lifeline, 2/0-3C, MC, Two-Hour Fire Rated Cables

General Description

Lifeline MC fire resistive cables were designed to meet and have successfully passed the two-hour fire rating certification test per UL 2196, Standard for Tests for Fire Resistive Cables. Lifeline MC Cables are preferred over Mineral Insulated (MI) cables, concrete encasement or the construction of fire rated assemblies based on the facts that Lifeline MC Cables are less costly and easier to install for many applications. Fire resistive cables are required per NFPA 70, Articles 517, 695, 700, 708, 728 and 760 as well as NFPA 72 and NFPA 101.

Applications
- Emergency Feeder Cables
- Tall Buildings
- Stairwell Pressurization
- Elevators / OEO
- Fire Pumps

- Ventilating Fans
- Exit Lighting
- Emergency lighting for roadway and transmit tunnels when cables include optional LSZH jacket over armor



Specs and Ratings:
Listed to UL 1569, Metal Clad Cables, as the following type:
- Type MC 600 Volt, Rated 90°C
- For Wet Locations
- For Cable Tray Use IEEE 1202/ FT4 Rated, ST1 Limited Smoke
- Classified to UL 2196, Standard for Tests for Fire Resistive Cables, for two-hours installations
- Electrical Circuit Integrity System (FHIT) No. 50 of the UL Fire Resistance Directory
- NFPA 70, NFPA 101 compliant
- Corrugated Copper Armor meets Equipment Grounding Conductor requirements of NEC Table 250.122



Conductor Size: 2/0 AWG
Conductors: 3
Conductor Material: Bare Stranded Copper
Insulation Material: Ceramifiable Silicone Zero Halogen (LSZH)
Outside Diameter: 1.85 Inches
Ampacity 75°C: 175
Ampacity 90°C: 195
Inner Binder Jacket: Ceramifiable Silicone Zero Halogen (LSZH)
Armor: Continuously Welded and Corrugated Copper
Net Weight: 1.90 lbs per ft

Spec Sheet

Belden 9841 Spec SheetView Spec Sheet for Complete Details

 

More Information
# of Conductors3 Conductors