500, 500, 500 & 350 Wofford Aluminum Quadruplex URD Direct Burial Cable
$
17.460000
17.460000
/ftProduct Details
Learn everything you want to know about this product to make an informed purchase
Specifications
-
Wire Size
500 MCM
-
# of Conductors
4 Conductors
-
Conductor Material
Aluminum
-
Stranded or Solid
Stranded
-
O.D. (Inches)
2.348
-
Ampacity
467
-
Voltage
600V
-
Insulation Material
XLPE - Cross-linked Polyethylene
-
Direct Burial
Yes
-
Sunlight Resistant
Yes
More information
500, 500, 500, & 350 Underground Secondary Distribution Cable
Color:
Black
Description:
Underground Secondary Distribution Cables are twisted assemblies of alloy 1350 aluminum conductors insulated with cross-linked polyethylene. They are used in various underground applications in secondary distribution circuits.
Conductor:
Compressed Class B compressed stranded, 1350 series aluminum alloy.
Insulation:
Black cross-linked polyethylene (XLPE)
Assembly:
Phase conductors and neutral conductors are cabled together to form a twisted assembly.
Applicable Standards:
- UL 854: Service Entrance Cables
- ICEA S-105-692 Standard for 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables
500, 500, 500, & 350 Quadruplex URD Cable Specifications*:
Phase Conductor-Size: 500 MCM
Conductor Strand: 37
Neutral Conductor-Size: 350 MCM
Conductor Strand: 37
Insulation Thickness: 0.095 inches
Outside Diameter: 2.348 inches
Allowable Ampacity-Direct Burial: 467 Amps
Allowable Ampacity-In Duct: 420 Amps
Weight: 2.174 lbs per ft
*Data provided on this page is subject to change based on different manufacturers variances.