Out Of Stock
10/3C Type MC-HL Aluminum Armored Cable w/ PVC Jacket
Product Details
Learn everything you want to know about this product to make an informed purchase10/3C Type MC-HL Aluminum Armored Cable w/ PVC Jacket - 3#14 Ground Wires
Applications:
Control and lighting circuits in manufacturing and processing plants, feeders in industrial and commercial distribution systems. May be directly buried or installed in cable tray or raceway.
Conductor:
Class B stranded, bare, annealed copper per ASTM B-3 and B-8
Insulation:
Cross-Linked Polyethylene (XLP) meeting the requirements of ICEA S-95-658 (NEMA WC70) and Type XHHW requirements of UL, color coding is Method 1, Table E-2
Assembly:
The insulated conductors and a single, uninsulated UL ground wire(s) are cabled with fillers to make round
Armor:
An impervious, corrugated continuous seam-welded aluminum alloy sheath in accordance with UL 1569. Armor is pressure-tested and meets the grounding requirements of NEC Article 250
Overall Jacket:
Black, sunlight-resistant Polyvinyl Chloride (PVC)
Ampacity:
Based on not more than three conductors in raceway or cable or earth and an ambient temperature of 30°C per NEC table 310.16. All multiconductor values have been derated per 2008 NEC Table 310.15(B)(2)(a) – TEMPERATURE: 90
Standards:
Cables are UL listed for cable tray use and meet the IEEE 1202 (70,000 Btu/hr) flame test. Individual conductors and completed cables are tested in accordance with UL 2225 requirements for Type MC-HL cables
Specifications*:
Size: 10 AWG
Conductor: 3 Conductor
Ground Wires: 3 #14AWG
Outside Diameter: 0.720 inches
Ampere Rating: 40
*Data provided on this page is subject to change based on different manufacturers variances.
Stocked | Yes |
---|---|
Wire Size | 10 AWG |
O.D. (Inches) | 0.72 |
Ampacity | 40 |