Okonite 161-23-6072, 1/0 Aluminum 35kv Underground Primary Distribution Cable, EPR, Full Neutral 100%, 345ML

SKU OK161-23-6072
How will you purchase this wire?
8.680000 8.680000
truck FREE SHIPPING ON ORDERS OVER $1000
MIN: 1 FT. | MAX: 10000 FT. 1 10000 tooltip To order multiple lengths, simply enter the desired footage into the quantity fields. Each length will be delivered on its own spool.

Please Select Color(s)

Multiple colors can be selected

....
Quantity

Select your preferred quantity for each color below. Add additional colors and lengths as needed.

Okonite 161-23-6072, 1/0 Aluminum 35kv Underground Primary Distribution Cable, EPR, Full Neutral 100%, 345ML

Color Length (ft.) Price
N/A

Length (ft.)

add Add a length
Grouped product items
Color Length (ft.)
N/A Length 500 ft.
truck FREE SHIPPING ON ORDERS OVER $1000
Product Details

Learn everything you want to know about this product to make an informed purchase

Specifications
  • Wire Size

    1/0 AWG

  • O.D. (Inches)

    1.44

  • Ampacity

    165

Data provided on this page is subject to change based on different manufacturers variances.
See Less
More information

35kV Underground Primary Distribution Cable-Jacketed Red Identification Stripes
Aluminum Conductor/105°C Rating
100% and 133% Insulation Levels

Applications:
Okoguard URO-J cables provide maximum circuit longevity in underground residential distribution systems. They can be buried di- rectly or installed in underground ducts or conduits.

Specifications:
Central Conductor: Aluminum per ASTM B-609, Class B stranded per B-231.

Conductor Screen: Extruded semiconduct- ing ethylene-propylene rubber meets or exceeds the requirements of ICEA S-94-649, AEIC CS8, and CSA C68.5.

Insulation: Extruded Okoguard meets or ex- ceeds the requirements of ICEA S-94-649, AEIC CS8, and CSA C68.5.

Insulation Screen: Extruded semiconduct- ing ethylene-propylene rubber meets or exceeds the requirements of ICEA S-94-649, AEIC CS8, and CSA C68.5.

Concentric Conductor: Bare copper wires.

Jacket: Black Okolene with red extruded stripes meets or exceeds the requirements of ICEA S-94-649, AEIC CS8, and CSA C68.5 for polyethylene jackets.

Insulation:
Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene rubber (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequaled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally inte- grated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service.

The triple tandem extrusion of the screens with the insulation provides optimum electri- cal characteristics.

An insulation screen of ethylene-propylene rubber is extruded over the insulation. The bare copper concentric wires are uniformly spaced around the insulation screen. The overall polyethylene jacket provides protec- tion against mechanical damage and corrosion.

Product identification is provided through the use of three red stripes placed 120° apart in the black jacket, with an NESC lightning bolt.

Voltage:  
35 kV

Specifications*:

Size: 1/0
Outside Diameter: 1.044 inches
Weight: 1.17 lbs per ft
Ampacity: Duct =  165 amps @ 90C

*Data provided on this page is subject to change based on different manufacturers variances.

See Less