750 MCM MV-105, 5kV/8kV, EPR/PVC Power Cable w/ Copper Tape Shield

SKU
MV105750-FT

Product Details

Learn everything you want to know about this product to make an informed purchase

Cut to length - sold by the foot. Enter the desired footage in the QTY box.
Minimum 100' to maximum 1000'. Please call for longer put ups.

Applications:
For use in power circuits up to 8 kV when installed in open air, conduit, duct or buried directly in the earth, for wet and dry locations. Used for power applications in chemical plants, refineries, steel mills, industrial plants, utility substations and generating stations.

Jacket:
Black Polyvinylchloride (PVC) Jacket, sunlight resistant

Standards:
Listed as Type MV-105 per UL 1072 and meets the requirements of ICEA S-93-639. Sizes 1/0 and larger marked "for CT use" and pass UL 1685 70,000 Btu/hr flame test

Conductors:
Class B stranded, annealed, bare copper per ASTM B-3 and B-8, (compact stranding per ASTM B-496 is available). Strand shield is an extruded semi-conducting thermoset

Insulation:
Ethylene Propylene Rubber (EPR) per ICEA S-93-639 (NEMA WC74)

Insulation Shield:
Extruded semi-conducting thermoset insulation shield. Metallic shield is a helically applied 5 mil uncoated copper tape

Ampacity:  
Based on three single conductor cables in isolated conduit in air per NEC Table 310.73 with a conductor temperature of 90°C and an ambient temperature of 40°C

Temperature:  
105°C

Voltage:  
5 kV 133% and 8 kV 100%

Specifications*:

Size: 750 MCM
Number of Strands: 61
Insulation Thickness: 0.115 inches
Jacket Thickness: 0.080 inches
Outside Diameter: 1.550 inches
Weight: 3.025 lbs per ft
Amps per Conductor: 600 amps

*Data provided on this page is subject to change based on different manufacturers variances.

More Information
StockedYes
Wire Size750 MCM
O.D. (Inches)1.55
Ampacity 600