In Stock
500MCM 3C w/ Ground Type MC Cable w/ PVC Jacket, Interlocked Armor Power Cable
Product Details
Learn everything you want to know about this product to make an informed purchase500 MCM 3C w/ Ground, Type MC Cable w/ PVC Jacket
600 Volt UL Type MC, CT USE, 90°C
XLP XHHW-2 Insulation
Aluminum Armor
Copper Conductors
Cut to length - sold by the foot. Enter the desired footage in the QTY box.
Minimum 50' to maximum 2500'. Please call for longer put ups.
Color:
Black
Applications:
For use in harsh environments where maximum conductor protection is required. Used for power, control and lighting circuits in a broad range of commercial and industrial pulp and paper, mining, and petroleum applications. Approved for use in wet or dry locations at 90°C, for installation indoors or outdoors, aerially, in conduits, ducts, cable trays or direct burial in circuits not exceeding 600 volts. May be used in NEC Class I and II, Division 2 and Class III, Division 1 and 2 hazardous locations. UL approved for use at 90°C for continuous operation, 130°C for emergency overload conditions, and 250°C for short circuit conditions. Aluminum interlocked armor cable is recommended as an economical alternative to wire in conduit systems.
Conductor:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8
Insulation:
Cross-linked polyethylene (XLP) per UL Standard 44 for Type XHHW-2 conductors
Jacket:
Black sunlight-resistant PVC per UL Standard 1569
Grounding Conductor:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 sized in accordance with UL Standard 1569
Armor:
Aluminum interlocked tape armor per UL 1569 and applicable ICEA standards, also available in galvanized steel armor
Flame Tests:
UL 1581 (70,000 BTU/hr) Flame Test
IEEE 1202 Flame Test
ICEA (210,000 BTU/hr) Flame Test
Color Code:
ICEA Method 4
Connectors:
• Explosion Proof, Class 1 Division 2: 424CU series – aluminum exterior components, nickel-plated brass interior components
• Rain Tight: 416MC series – all nickel-plated brass
Specifications*:
Size: 500 MCM
Number of Conductors: 3
Conductor Strand: 37
Ground Wire Size: 2 AWG
Minimum AVG Insulation Thickness: 0.065 inches
Minimum AVG Jacket Thickness: 0.075 inches
Armor Diameter: 2.31 inches
Overall Diameter: 2.46 inches
Net Weight: 6.795 lbs per ft
Class 1 Div. 2 Connector Number: 424CU09
Rain Tight Connector Number: 416MC09
*Data provided on this page is subject to change based on different manufacturers variances.
Stocked | Yes |
---|---|
Wire Size | 500 MCM |
# of Conductors | 3 Conductors w/ Ground |
O.D. (Inches) | 2.46 |